{"id":330,"date":"2016-12-08T12:13:06","date_gmt":"2016-12-08T12:13:06","guid":{"rendered":"http:\/\/www.the-regs.co.uk\/blog\/?p=330"},"modified":"2016-12-08T12:13:06","modified_gmt":"2016-12-08T12:13:06","slug":"protective-devices-circuit-breakers-and-fault-current","status":"publish","type":"post","link":"https:\/\/the-regs.co.uk\/blog\/?p=330","title":{"rendered":"Protective Devices. Circuit-Breakers and Fault Current"},"content":{"rendered":"<p>Circuit Breakers<\/p>\n<p>Perhaps the most common of all protective devices circuit-breakers are found in modern single-phase domestic consumer units and three-phase\u00a0industrial \/ commercial distribution boards.<\/p>\n<p>The British Standard BS EN 60898 applies to these devices and they usually\u00a0come in sizes of 2 A up to 125 A.<\/p>\n<p>Apart from its nominal rating (In)\u00a010 A, 16 A, 23 A etc we usually find two other values shown on the circuit breaker, they are\u00a0 Ics and Icn.<\/p>\n<p>Ics is the amount of current that the circuit breaker can safely withstand without being damaged for example 6 kA or 6000 A and remain usable.<\/p>\n<p>Icn is the amount of current the circuit-breaker can safely\u00a0handle but would not remain usable.<\/p>\n<p>So, if we have a 32 A circuit breaker with an Ics of 6 kA and an Icn of 10 kA this means that any fault current up to 6 kA (Ics)\u00a0would not damage the device and it would still be usable.\u00a0However, anything above 6 kA up to 10 kA would damage the device and render it unusable. Anything above 10 kA (Icn) can be dangerous and could cause the circuit-breaker to burst into flames or even explode.<\/p>\n<p>This is why prospective\u00a0fault current values (Ipf) are so important and should always be measured at the origin of the installation where &#8216;thanks to Ohm&#8217;s Law&#8217; they will always be the highest.<\/p>\n<p>See BS7671 Table 41.3 for common value ratings (In)\u00a0of BS EN 60898 circuit-breakers as well as their maximum Zs values.<\/p>\n<p>There is a balancing act that we perform when it comes to fault current. We need it to be high enough to trip the device within its maximum disconnection time but we don&#8217;t want it to be so high that it damages the installation\/devices.<\/p>\n<p>&nbsp;<\/p>\n<p>&nbsp;<\/p>\n","protected":false},"excerpt":{"rendered":"<p>Circuit Breakers Perhaps the most common of all protective devices circuit-breakers are found in modern single-phase domestic consumer units and three-phase\u00a0industrial \/ commercial distribution boards. The British Standard BS EN 60898 applies to these devices and they usually\u00a0come in sizes of 2 A up to 125 A. Apart from its nominal rating (In)\u00a010 A, 16&#8230;<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"_jetpack_newsletter_access":"","_jetpack_dont_email_post_to_subs":false,"_jetpack_newsletter_tier_id":0,"_jetpack_memberships_contains_paywalled_content":false,"_jetpack_memberships_contains_paid_content":false,"footnotes":""},"categories":[1],"tags":[],"class_list":["post-330","post","type-post","status-publish","format-standard","hentry","category-general","th-blog blog-single has-post-thumbnail"],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v28.0 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>Protective Devices. Circuit-Breakers and Fault Current - the-Regs : BS7671 18th Edition Online Training<\/title>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/the-regs.co.uk\/blog\/?p=330\" \/>\n<meta property=\"og:locale\" content=\"en_GB\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Protective Devices. Circuit-Breakers and Fault Current - the-Regs : BS7671 18th Edition Online Training\" \/>\n<meta property=\"og:description\" content=\"Circuit Breakers Perhaps the most common of all protective devices circuit-breakers are found in modern single-phase domestic consumer units and three-phase\u00a0industrial \/ commercial distribution boards. The British Standard BS EN 60898 applies to these devices and they usually\u00a0come in sizes of 2 A up to 125 A. Apart from its nominal rating (In)\u00a010 A, 16...\" \/>\n<meta property=\"og:url\" content=\"https:\/\/the-regs.co.uk\/blog\/?p=330\" \/>\n<meta property=\"og:site_name\" content=\"the-Regs : BS7671 18th Edition Online Training\" \/>\n<meta property=\"article:published_time\" content=\"2016-12-08T12:13:06+00:00\" \/>\n<meta name=\"author\" content=\"the Regs Guy\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:creator\" content=\"@theregsguy\" \/>\n<meta name=\"twitter:site\" content=\"@theregsguy\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"the Regs Guy\" \/>\n\t<meta name=\"twitter:label2\" content=\"Estimated reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"1 minute\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/?p=330#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/?p=330\"},\"author\":{\"name\":\"the Regs Guy\",\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/#\\\/schema\\\/person\\\/0d7feabc48e1ab05b0c346e599ea65cf\"},\"headline\":\"Protective Devices. Circuit-Breakers and Fault Current\",\"datePublished\":\"2016-12-08T12:13:06+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/?p=330\"},\"wordCount\":291,\"commentCount\":0,\"publisher\":{\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/#organization\"},\"articleSection\":[\"General\"],\"inLanguage\":\"en-GB\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/?p=330#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/?p=330\",\"url\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/?p=330\",\"name\":\"Protective Devices. Circuit-Breakers and Fault Current - the-Regs : BS7671 18th Edition Online Training\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/#website\"},\"datePublished\":\"2016-12-08T12:13:06+00:00\",\"breadcrumb\":{\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/?p=330#breadcrumb\"},\"inLanguage\":\"en-GB\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/?p=330\"]}]},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/?p=330#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Protective Devices. Circuit-Breakers and Fault Current\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/#website\",\"url\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/\",\"name\":\"the-Regs.co.uk 18th Edition Online Training Specialist\",\"description\":\"BS 7671: 18th Edition Wiring Regulations - Study when you want and pass your exam  when you&#039;re ready...\",\"publisher\":{\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/#organization\"},\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-GB\"},{\"@type\":\"Organization\",\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/#organization\",\"name\":\"the-Regs : BS7671 18th Edition Online Training\",\"url\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/\",\"logo\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-GB\",\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/#\\\/schema\\\/logo\\\/image\\\/\",\"url\":\"https:\\\/\\\/i0.wp.com\\\/the-regs.co.uk\\\/blog\\\/wp-content\\\/uploads\\\/2025\\\/10\\\/favicon-192x192-1.png?fit=192%2C192&ssl=1\",\"contentUrl\":\"https:\\\/\\\/i0.wp.com\\\/the-regs.co.uk\\\/blog\\\/wp-content\\\/uploads\\\/2025\\\/10\\\/favicon-192x192-1.png?fit=192%2C192&ssl=1\",\"width\":192,\"height\":192,\"caption\":\"the-Regs : BS7671 18th Edition Online Training\"},\"image\":{\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/#\\\/schema\\\/logo\\\/image\\\/\"},\"sameAs\":[\"https:\\\/\\\/x.com\\\/theregsguy\"]},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/#\\\/schema\\\/person\\\/0d7feabc48e1ab05b0c346e599ea65cf\",\"name\":\"the Regs Guy\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-GB\",\"@id\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/f10b538b4ce6fdea13c84ac1ce266ae912ec071c6775b6ce8df5fdad3ac24bb0?s=96&d=mm&r=g\",\"url\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/f10b538b4ce6fdea13c84ac1ce266ae912ec071c6775b6ce8df5fdad3ac24bb0?s=96&d=mm&r=g\",\"contentUrl\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/f10b538b4ce6fdea13c84ac1ce266ae912ec071c6775b6ce8df5fdad3ac24bb0?s=96&d=mm&r=g\",\"caption\":\"the Regs Guy\"},\"description\":\"A professional qualified electrician with nearly forty years of under paid, hard work within the electrical installation industry. I've also been a successful electrical installation tutor since 2008. Delivering both City &amp; Guilds \\\/ EAL level 3 courses including \\\"18th Edition Wiring Regulations, Inspection &amp; Testing (initial verification and periodic inspection, testing and reporting), Building Regulations, PAT and Part P etc.\\\" both in the private sector and local FE colleges. I've also been running my own training center since 2015. See www.waybrite.co.uk\",\"sameAs\":[\"http:\\\/\\\/www.the-regs.co.uk\"],\"url\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/?author=1\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Protective Devices. Circuit-Breakers and Fault Current - the-Regs : BS7671 18th Edition Online Training","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/the-regs.co.uk\/blog\/?p=330","og_locale":"en_GB","og_type":"article","og_title":"Protective Devices. Circuit-Breakers and Fault Current - the-Regs : BS7671 18th Edition Online Training","og_description":"Circuit Breakers Perhaps the most common of all protective devices circuit-breakers are found in modern single-phase domestic consumer units and three-phase\u00a0industrial \/ commercial distribution boards. The British Standard BS EN 60898 applies to these devices and they usually\u00a0come in sizes of 2 A up to 125 A. Apart from its nominal rating (In)\u00a010 A, 16...","og_url":"https:\/\/the-regs.co.uk\/blog\/?p=330","og_site_name":"the-Regs : BS7671 18th Edition Online Training","article_published_time":"2016-12-08T12:13:06+00:00","author":"the Regs Guy","twitter_card":"summary_large_image","twitter_creator":"@theregsguy","twitter_site":"@theregsguy","twitter_misc":{"Written by":"the Regs Guy","Estimated reading time":"1 minute"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/the-regs.co.uk\/blog\/?p=330#article","isPartOf":{"@id":"https:\/\/the-regs.co.uk\/blog\/?p=330"},"author":{"name":"the Regs Guy","@id":"https:\/\/the-regs.co.uk\/blog\/#\/schema\/person\/0d7feabc48e1ab05b0c346e599ea65cf"},"headline":"Protective Devices. Circuit-Breakers and Fault Current","datePublished":"2016-12-08T12:13:06+00:00","mainEntityOfPage":{"@id":"https:\/\/the-regs.co.uk\/blog\/?p=330"},"wordCount":291,"commentCount":0,"publisher":{"@id":"https:\/\/the-regs.co.uk\/blog\/#organization"},"articleSection":["General"],"inLanguage":"en-GB","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/the-regs.co.uk\/blog\/?p=330#respond"]}]},{"@type":"WebPage","@id":"https:\/\/the-regs.co.uk\/blog\/?p=330","url":"https:\/\/the-regs.co.uk\/blog\/?p=330","name":"Protective Devices. Circuit-Breakers and Fault Current - the-Regs : BS7671 18th Edition Online Training","isPartOf":{"@id":"https:\/\/the-regs.co.uk\/blog\/#website"},"datePublished":"2016-12-08T12:13:06+00:00","breadcrumb":{"@id":"https:\/\/the-regs.co.uk\/blog\/?p=330#breadcrumb"},"inLanguage":"en-GB","potentialAction":[{"@type":"ReadAction","target":["https:\/\/the-regs.co.uk\/blog\/?p=330"]}]},{"@type":"BreadcrumbList","@id":"https:\/\/the-regs.co.uk\/blog\/?p=330#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/the-regs.co.uk\/blog"},{"@type":"ListItem","position":2,"name":"Protective Devices. Circuit-Breakers and Fault Current"}]},{"@type":"WebSite","@id":"https:\/\/the-regs.co.uk\/blog\/#website","url":"https:\/\/the-regs.co.uk\/blog\/","name":"the-Regs.co.uk 18th Edition Online Training Specialist","description":"BS 7671: 18th Edition Wiring Regulations - Study when you want and pass your exam  when you&#039;re ready...","publisher":{"@id":"https:\/\/the-regs.co.uk\/blog\/#organization"},"potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/the-regs.co.uk\/blog\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-GB"},{"@type":"Organization","@id":"https:\/\/the-regs.co.uk\/blog\/#organization","name":"the-Regs : BS7671 18th Edition Online Training","url":"https:\/\/the-regs.co.uk\/blog\/","logo":{"@type":"ImageObject","inLanguage":"en-GB","@id":"https:\/\/the-regs.co.uk\/blog\/#\/schema\/logo\/image\/","url":"https:\/\/i0.wp.com\/the-regs.co.uk\/blog\/wp-content\/uploads\/2025\/10\/favicon-192x192-1.png?fit=192%2C192&ssl=1","contentUrl":"https:\/\/i0.wp.com\/the-regs.co.uk\/blog\/wp-content\/uploads\/2025\/10\/favicon-192x192-1.png?fit=192%2C192&ssl=1","width":192,"height":192,"caption":"the-Regs : BS7671 18th Edition Online Training"},"image":{"@id":"https:\/\/the-regs.co.uk\/blog\/#\/schema\/logo\/image\/"},"sameAs":["https:\/\/x.com\/theregsguy"]},{"@type":"Person","@id":"https:\/\/the-regs.co.uk\/blog\/#\/schema\/person\/0d7feabc48e1ab05b0c346e599ea65cf","name":"the Regs Guy","image":{"@type":"ImageObject","inLanguage":"en-GB","@id":"https:\/\/secure.gravatar.com\/avatar\/f10b538b4ce6fdea13c84ac1ce266ae912ec071c6775b6ce8df5fdad3ac24bb0?s=96&d=mm&r=g","url":"https:\/\/secure.gravatar.com\/avatar\/f10b538b4ce6fdea13c84ac1ce266ae912ec071c6775b6ce8df5fdad3ac24bb0?s=96&d=mm&r=g","contentUrl":"https:\/\/secure.gravatar.com\/avatar\/f10b538b4ce6fdea13c84ac1ce266ae912ec071c6775b6ce8df5fdad3ac24bb0?s=96&d=mm&r=g","caption":"the Regs Guy"},"description":"A professional qualified electrician with nearly forty years of under paid, hard work within the electrical installation industry. I've also been a successful electrical installation tutor since 2008. Delivering both City &amp; Guilds \/ EAL level 3 courses including \"18th Edition Wiring Regulations, Inspection &amp; Testing (initial verification and periodic inspection, testing and reporting), Building Regulations, PAT and Part P etc.\" both in the private sector and local FE colleges. I've also been running my own training center since 2015. See www.waybrite.co.uk","sameAs":["http:\/\/www.the-regs.co.uk"],"url":"https:\/\/the-regs.co.uk\/blog\/?author=1"}]}},"jetpack_featured_media_url":"","jetpack_shortlink":"https:\/\/wp.me\/p32IMi-5k","jetpack_sharing_enabled":true,"jetpack-related-posts":[],"_links":{"self":[{"href":"https:\/\/the-regs.co.uk\/blog\/index.php?rest_route=\/wp\/v2\/posts\/330","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/the-regs.co.uk\/blog\/index.php?rest_route=\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/the-regs.co.uk\/blog\/index.php?rest_route=\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/the-regs.co.uk\/blog\/index.php?rest_route=\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/the-regs.co.uk\/blog\/index.php?rest_route=%2Fwp%2Fv2%2Fcomments&post=330"}],"version-history":[{"count":0,"href":"https:\/\/the-regs.co.uk\/blog\/index.php?rest_route=\/wp\/v2\/posts\/330\/revisions"}],"wp:attachment":[{"href":"https:\/\/the-regs.co.uk\/blog\/index.php?rest_route=%2Fwp%2Fv2%2Fmedia&parent=330"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/the-regs.co.uk\/blog\/index.php?rest_route=%2Fwp%2Fv2%2Fcategories&post=330"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/the-regs.co.uk\/blog\/index.php?rest_route=%2Fwp%2Fv2%2Ftags&post=330"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}