{"id":495,"date":"2018-10-12T09:46:59","date_gmt":"2018-10-12T09:46:59","guid":{"rendered":"https:\/\/the-regs.co.uk\/blog\/?p=495"},"modified":"2018-10-12T09:46:59","modified_gmt":"2018-10-12T09:46:59","slug":"rcd-protection-in-domestic-installations","status":"publish","type":"post","link":"https:\/\/the-regs.co.uk\/blog\/?p=495","title":{"rendered":"RCD Protection in Domestic Installations"},"content":{"rendered":"<p><span style=\"font-family: Helvetica, Arial, sans-serif;\">Within domestic installations there are numerous regulations within BS 7671:2018 concerning additional protection through the use of 30mA RCDs&#8230;<\/span><\/p>\n<p><span style=\"font-family: Helvetica, Arial, sans-serif;\"><strong>411.3.3:<\/strong> Gives us additional protection via a 30 mA RCD for &#8216;general&#8217; sockets, both indoor and outdoors.<\/span><\/p>\n<p><span style=\"font-family: Helvetica, Arial, sans-serif;\"><strong>411.3.4:<\/strong> Again 30 mA RCD additional protection for all lighting circuits.<\/span><\/p>\n<p><span style=\"font-family: Helvetica, Arial, sans-serif;\"><strong>522.6.202:<\/strong> Cables buried in a wall less than 50mm from the surface that are run in the prescribed cable zones see 522.6.202 (i) but are not mechanically protected by any of the methods within 522.6.204 (i) to (iv) or are extra-low voltage 522.6.204 (vi) shall be provided with additional protection as in 415.1.1 &#8217;30mA RCD&#8217;.<\/span><\/p>\n<p><span style=\"font-family: Helvetica, Arial, sans-serif;\"><strong>701.411.3.3.<\/strong> Any circuits serving a room containing a bath or shower (ie lights and shower etc) and any circuits that pass through zones 1 or 2 shall have one or more 30mA RCDs providing additional protection. There is no requirement to put showers on their own RCD such as a 45A \/ 30mA RCBO and they can be grouped with the rest of the circuits and provided with additional protected with a 30mA RCCB, but it may be considered as a good practice to do so.<br \/>\n<\/span><\/p>\n<p><span style=\"font-family: Helvetica, Arial, sans-serif;\">These regulations ensure that all circuits within a domestic installation should be provided with additional protection via a 30 mA RCD which can either be through the use of RCCBs which provide additional protection to multiple circuits, with overload protection provided by the individual circuit breakers. Or by the use of RCBOs which will provide individual &#8216;RCD and overload&#8217; circuit protection.<\/span><\/p>\n<p><span style=\"font-family: Helvetica, Arial, sans-serif;\"><strong>NOTE: 30mA RCD&#8217;s<\/strong> are used for additional protection because potentially any <strong>fault current of 50mA (0.05A) or more can be fatal<\/strong>. So 30mA RCDs are there to provide additional protection for people and not the installation, and domestic installations are full of unskilled and unsupervised people who are unaware of the potential dangers of electricity and need to provided with additional protection.<\/span><\/p>\n","protected":false},"excerpt":{"rendered":"<p>Within domestic installations there are numerous regulations within BS 7671:2018 concerning additional protection through the use of 30mA RCDs&#8230; 411.3.3: Gives us additional protection via a 30 mA RCD for &#8216;general&#8217; sockets, both indoor and outdoors. 411.3.4: Again 30 mA RCD additional protection for all lighting circuits. 522.6.202: Cables buried in a wall less than&#8230;<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"_jetpack_newsletter_access":"","_jetpack_dont_email_post_to_subs":false,"_jetpack_newsletter_tier_id":0,"_jetpack_memberships_contains_paywalled_content":false,"_jetpack_memberships_contains_paid_content":false,"footnotes":""},"categories":[19,1],"tags":[],"class_list":["post-495","post","type-post","status-publish","format-standard","hentry","category-18th-edition-bs7671-wiring-regulations","category-general","th-blog blog-single has-post-thumbnail"],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v28.0 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>RCD Protection in Domestic Installations - the-Regs : BS7671 18th Edition Online Training<\/title>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/the-regs.co.uk\/blog\/?p=495\" \/>\n<meta property=\"og:locale\" content=\"en_GB\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"RCD Protection in Domestic Installations - the-Regs : BS7671 18th Edition Online Training\" \/>\n<meta property=\"og:description\" content=\"Within domestic installations there are numerous regulations within BS 7671:2018 concerning additional protection through the use of 30mA RCDs&#8230; 411.3.3: Gives us additional protection via a 30 mA RCD for &#8216;general&#8217; sockets, both indoor and outdoors. 411.3.4: Again 30 mA RCD additional protection for all lighting circuits. 522.6.202: Cables buried in a wall less than...\" \/>\n<meta property=\"og:url\" content=\"https:\/\/the-regs.co.uk\/blog\/?p=495\" \/>\n<meta property=\"og:site_name\" content=\"the-Regs : BS7671 18th Edition Online Training\" \/>\n<meta property=\"article:published_time\" content=\"2018-10-12T09:46:59+00:00\" \/>\n<meta name=\"author\" content=\"the Regs Guy\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:creator\" content=\"@theregsguy\" \/>\n<meta name=\"twitter:site\" content=\"@theregsguy\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"the Regs Guy\" \/>\n\t<meta name=\"twitter:label2\" content=\"Estimated reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"1 minute\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/?p=495#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/?p=495\"},\"author\":{\"name\":\"the Regs Guy\",\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/#\\\/schema\\\/person\\\/0d7feabc48e1ab05b0c346e599ea65cf\"},\"headline\":\"RCD Protection in Domestic Installations\",\"datePublished\":\"2018-10-12T09:46:59+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/?p=495\"},\"wordCount\":302,\"commentCount\":0,\"publisher\":{\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/#organization\"},\"articleSection\":[\"18th Edition BS7671\",\"General\"],\"inLanguage\":\"en-GB\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/?p=495#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/?p=495\",\"url\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/?p=495\",\"name\":\"RCD Protection in Domestic Installations - the-Regs : BS7671 18th Edition Online Training\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/#website\"},\"datePublished\":\"2018-10-12T09:46:59+00:00\",\"breadcrumb\":{\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/?p=495#breadcrumb\"},\"inLanguage\":\"en-GB\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/?p=495\"]}]},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/?p=495#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"RCD Protection in Domestic Installations\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/#website\",\"url\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/\",\"name\":\"the-Regs.co.uk 18th Edition Online Training Specialist\",\"description\":\"BS 7671: 18th Edition Wiring Regulations - Study when you want and pass your exam  when you&#039;re ready...\",\"publisher\":{\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/#organization\"},\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-GB\"},{\"@type\":\"Organization\",\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/#organization\",\"name\":\"the-Regs : BS7671 18th Edition Online Training\",\"url\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/\",\"logo\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-GB\",\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/#\\\/schema\\\/logo\\\/image\\\/\",\"url\":\"https:\\\/\\\/i0.wp.com\\\/the-regs.co.uk\\\/blog\\\/wp-content\\\/uploads\\\/2025\\\/10\\\/favicon-192x192-1.png?fit=192%2C192&ssl=1\",\"contentUrl\":\"https:\\\/\\\/i0.wp.com\\\/the-regs.co.uk\\\/blog\\\/wp-content\\\/uploads\\\/2025\\\/10\\\/favicon-192x192-1.png?fit=192%2C192&ssl=1\",\"width\":192,\"height\":192,\"caption\":\"the-Regs : BS7671 18th Edition Online Training\"},\"image\":{\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/#\\\/schema\\\/logo\\\/image\\\/\"},\"sameAs\":[\"https:\\\/\\\/x.com\\\/theregsguy\"]},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/#\\\/schema\\\/person\\\/0d7feabc48e1ab05b0c346e599ea65cf\",\"name\":\"the Regs Guy\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-GB\",\"@id\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/f10b538b4ce6fdea13c84ac1ce266ae912ec071c6775b6ce8df5fdad3ac24bb0?s=96&d=mm&r=g\",\"url\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/f10b538b4ce6fdea13c84ac1ce266ae912ec071c6775b6ce8df5fdad3ac24bb0?s=96&d=mm&r=g\",\"contentUrl\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/f10b538b4ce6fdea13c84ac1ce266ae912ec071c6775b6ce8df5fdad3ac24bb0?s=96&d=mm&r=g\",\"caption\":\"the Regs Guy\"},\"description\":\"A professional qualified electrician with nearly forty years of under paid, hard work within the electrical installation industry. I've also been a successful electrical installation tutor since 2008. Delivering both City &amp; Guilds \\\/ EAL level 3 courses including \\\"18th Edition Wiring Regulations, Inspection &amp; Testing (initial verification and periodic inspection, testing and reporting), Building Regulations, PAT and Part P etc.\\\" both in the private sector and local FE colleges. I've also been running my own training center since 2015. See www.waybrite.co.uk\",\"sameAs\":[\"http:\\\/\\\/www.the-regs.co.uk\"],\"url\":\"https:\\\/\\\/the-regs.co.uk\\\/blog\\\/?author=1\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"RCD Protection in Domestic Installations - the-Regs : BS7671 18th Edition Online Training","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/the-regs.co.uk\/blog\/?p=495","og_locale":"en_GB","og_type":"article","og_title":"RCD Protection in Domestic Installations - the-Regs : BS7671 18th Edition Online Training","og_description":"Within domestic installations there are numerous regulations within BS 7671:2018 concerning additional protection through the use of 30mA RCDs&#8230; 411.3.3: Gives us additional protection via a 30 mA RCD for &#8216;general&#8217; sockets, both indoor and outdoors. 411.3.4: Again 30 mA RCD additional protection for all lighting circuits. 522.6.202: Cables buried in a wall less than...","og_url":"https:\/\/the-regs.co.uk\/blog\/?p=495","og_site_name":"the-Regs : BS7671 18th Edition Online Training","article_published_time":"2018-10-12T09:46:59+00:00","author":"the Regs Guy","twitter_card":"summary_large_image","twitter_creator":"@theregsguy","twitter_site":"@theregsguy","twitter_misc":{"Written by":"the Regs Guy","Estimated reading time":"1 minute"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/the-regs.co.uk\/blog\/?p=495#article","isPartOf":{"@id":"https:\/\/the-regs.co.uk\/blog\/?p=495"},"author":{"name":"the Regs Guy","@id":"https:\/\/the-regs.co.uk\/blog\/#\/schema\/person\/0d7feabc48e1ab05b0c346e599ea65cf"},"headline":"RCD Protection in Domestic Installations","datePublished":"2018-10-12T09:46:59+00:00","mainEntityOfPage":{"@id":"https:\/\/the-regs.co.uk\/blog\/?p=495"},"wordCount":302,"commentCount":0,"publisher":{"@id":"https:\/\/the-regs.co.uk\/blog\/#organization"},"articleSection":["18th Edition BS7671","General"],"inLanguage":"en-GB","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/the-regs.co.uk\/blog\/?p=495#respond"]}]},{"@type":"WebPage","@id":"https:\/\/the-regs.co.uk\/blog\/?p=495","url":"https:\/\/the-regs.co.uk\/blog\/?p=495","name":"RCD Protection in Domestic Installations - the-Regs : BS7671 18th Edition Online Training","isPartOf":{"@id":"https:\/\/the-regs.co.uk\/blog\/#website"},"datePublished":"2018-10-12T09:46:59+00:00","breadcrumb":{"@id":"https:\/\/the-regs.co.uk\/blog\/?p=495#breadcrumb"},"inLanguage":"en-GB","potentialAction":[{"@type":"ReadAction","target":["https:\/\/the-regs.co.uk\/blog\/?p=495"]}]},{"@type":"BreadcrumbList","@id":"https:\/\/the-regs.co.uk\/blog\/?p=495#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/the-regs.co.uk\/blog"},{"@type":"ListItem","position":2,"name":"RCD Protection in Domestic Installations"}]},{"@type":"WebSite","@id":"https:\/\/the-regs.co.uk\/blog\/#website","url":"https:\/\/the-regs.co.uk\/blog\/","name":"the-Regs.co.uk 18th Edition Online Training Specialist","description":"BS 7671: 18th Edition Wiring Regulations - Study when you want and pass your exam  when you&#039;re ready...","publisher":{"@id":"https:\/\/the-regs.co.uk\/blog\/#organization"},"potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/the-regs.co.uk\/blog\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-GB"},{"@type":"Organization","@id":"https:\/\/the-regs.co.uk\/blog\/#organization","name":"the-Regs : BS7671 18th Edition Online Training","url":"https:\/\/the-regs.co.uk\/blog\/","logo":{"@type":"ImageObject","inLanguage":"en-GB","@id":"https:\/\/the-regs.co.uk\/blog\/#\/schema\/logo\/image\/","url":"https:\/\/i0.wp.com\/the-regs.co.uk\/blog\/wp-content\/uploads\/2025\/10\/favicon-192x192-1.png?fit=192%2C192&ssl=1","contentUrl":"https:\/\/i0.wp.com\/the-regs.co.uk\/blog\/wp-content\/uploads\/2025\/10\/favicon-192x192-1.png?fit=192%2C192&ssl=1","width":192,"height":192,"caption":"the-Regs : BS7671 18th Edition Online Training"},"image":{"@id":"https:\/\/the-regs.co.uk\/blog\/#\/schema\/logo\/image\/"},"sameAs":["https:\/\/x.com\/theregsguy"]},{"@type":"Person","@id":"https:\/\/the-regs.co.uk\/blog\/#\/schema\/person\/0d7feabc48e1ab05b0c346e599ea65cf","name":"the Regs Guy","image":{"@type":"ImageObject","inLanguage":"en-GB","@id":"https:\/\/secure.gravatar.com\/avatar\/f10b538b4ce6fdea13c84ac1ce266ae912ec071c6775b6ce8df5fdad3ac24bb0?s=96&d=mm&r=g","url":"https:\/\/secure.gravatar.com\/avatar\/f10b538b4ce6fdea13c84ac1ce266ae912ec071c6775b6ce8df5fdad3ac24bb0?s=96&d=mm&r=g","contentUrl":"https:\/\/secure.gravatar.com\/avatar\/f10b538b4ce6fdea13c84ac1ce266ae912ec071c6775b6ce8df5fdad3ac24bb0?s=96&d=mm&r=g","caption":"the Regs Guy"},"description":"A professional qualified electrician with nearly forty years of under paid, hard work within the electrical installation industry. I've also been a successful electrical installation tutor since 2008. Delivering both City &amp; Guilds \/ EAL level 3 courses including \"18th Edition Wiring Regulations, Inspection &amp; Testing (initial verification and periodic inspection, testing and reporting), Building Regulations, PAT and Part P etc.\" both in the private sector and local FE colleges. I've also been running my own training center since 2015. See www.waybrite.co.uk","sameAs":["http:\/\/www.the-regs.co.uk"],"url":"https:\/\/the-regs.co.uk\/blog\/?author=1"}]}},"jetpack_featured_media_url":"","jetpack_shortlink":"https:\/\/wp.me\/p32IMi-7Z","jetpack_sharing_enabled":true,"jetpack-related-posts":[],"_links":{"self":[{"href":"https:\/\/the-regs.co.uk\/blog\/index.php?rest_route=\/wp\/v2\/posts\/495","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/the-regs.co.uk\/blog\/index.php?rest_route=\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/the-regs.co.uk\/blog\/index.php?rest_route=\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/the-regs.co.uk\/blog\/index.php?rest_route=\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/the-regs.co.uk\/blog\/index.php?rest_route=%2Fwp%2Fv2%2Fcomments&post=495"}],"version-history":[{"count":0,"href":"https:\/\/the-regs.co.uk\/blog\/index.php?rest_route=\/wp\/v2\/posts\/495\/revisions"}],"wp:attachment":[{"href":"https:\/\/the-regs.co.uk\/blog\/index.php?rest_route=%2Fwp%2Fv2%2Fmedia&parent=495"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/the-regs.co.uk\/blog\/index.php?rest_route=%2Fwp%2Fv2%2Fcategories&post=495"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/the-regs.co.uk\/blog\/index.php?rest_route=%2Fwp%2Fv2%2Ftags&post=495"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}