Domestic Maximum Demand

BS7671 Part 3 Chapter 31 Purpose, Supplies and Structure

311 Maximum Demand and Diversity

Regulation 311.1 …….. In determining the maximum demand of an installation diversity may be taken into account.

What this means is that not everything will be switched on at the same time and we can make allowances for that.

Domestic installations:

Applying diversity to the maximum load (Amps)

Lighting: 66%
Heating: 100% of total up to 10A and 50% of all above
Cooking: 10A + 30% of cooker full load above 10A and + 5A if there is a cooker socket
Water Heaters: (Instant – eg. showers) 100% of largest + 100% second largest + 25% of remaining
Water Heaters: (Immersion cylinder) 100%
Floor: 100%
Storage Heaters: 100%
Sockets: 100% of largest appliance + 40% at every other point